Brengt ultraschone lucht op de OK meer veiligheid?

F.H. van Tiel, A. G. Buiting, N. E. Meessen, A. Voss, M.C. Vos

Research output: Contribution to journalArticleAcademicpeer-review

Abstract

The Dutch quality control plan for climatisation of the operating room (OR), which was published in 2005, describes the management and maintenance of the air conditioning system. This management plan proposes a standard for air quality in class 1 ORs. This has been adopted by the Dutch Orthopaedic Society, but not by other surgical societies. The British study which underlies the proposed norm for air quality in class 1 ORs, a study on the infection preventive effect of ultraclean air, dates from 1982 and is inadequately controlled for prophylactic use of antibiotics. Antibiotic prophylaxis in itself already reduces the number of surgical site infections.-More recent studies fail to show an infection preventive effect of ultraclean air in the OR. The Dutch Working Party for Infection Prevention (WIP) ought to take the initiative, together with the medical Scientific Societies and the Society of Infection Prevention and Control in the health care setting (VHIG), to establish enforceable norms for microbiological air quality and to set criteria as to which types of operations are allowed to be performed in which class of OR.
Original languageEnglish
Pages (from-to)1-5
JournalNederlands Tijdschrift voor Geneeskunde
Volume154
Issue numberA1598
Publication statusPublished - 1 Jan 2010